NV - Boulder City - Amendments, 0
- Article 100 Definitions
- Add a new definition to article 100, as follows:
- Installed conductors or cables that are not terminated at both ends at a connector or other equipment and not identified for future use with a tag.
- Section 110.12 Mechanical Execution of Work.
- Section 210.8(B) Other Than Dwelling Units.
- Section 210.23 Permissible Loads.
- Add a new Subsection (E) to Section 210.23, as follows:
- (E) Dwelling Branch Circuits
- (1) Maximum Number (15-ampere). The maximum number of outlets on a 15-
- ampere, 125 volt (nominal) luminaire circuit shall be twelve (12) and shall not contain general purpose receptacle outlets.
- Exception No. 1: Dedicated branch circuits feeding only IC rated recessed luminaires and/or low wattage energy efficient luminaires may use Article 220.14(D) for computing the maximum number of luminaire outlets.
- Exception No. 2: In branch circuits serving smoke detectors the smoke detector outlets need not be counted with other luminaire outlets.
- Exception No. 3: As an alternate, receptacles may be included at the discretion of the Building Official subject to approved circuited plans including maximum 5% voltage drop at 80% of overcurrent device rating.
- (2) Maximum Number (20-ampere). The maximum number of outlets on a 20 ampere, 125-volt (nominal) circuit used exclusively for receptacles, for luminaire outlets or for any combination of receptacles and luminaire outlets shall be twelve (12).
- Exception No. 1: Dedicated branch circuits feeding only IC rated recessed luminaires and/or low wattage energy efficient luminaires may use Article 220.14(D) for computing the maximum number of luminaire outlets.
- Exception No. 2: In branch circuits serving smoke detectors the smoke detectors need not be counted with the other luminaire and/or receptacle outlets.
- (3) Individual Branch Circuits. The following fastened-in-place appliances are required to have a separate minimum 20-ampere circuit: dishwasher, trash compactor and microwave oven. The required laundry circuit may serve one (1) additional outlet ...
- Section 210.52(A)(2) Wall Space.
- Revise Section 210.52(A)(2), as follows:
- Section 210.52(F) Laundry Areas.
- Add a new exception No. 3 to Section 210.52(F), as follows:
- Section 210.70(A)(1) Habitable Rooms.
- Revise Item (1) in Section 210.70(A), as follows:
- Section 210.70(A)(2) Additional Locations.
- Revise item (a) in Section 210.70(A)(2):
- Revise item (b) in Section 210.70(A)(2), as follows:
- Section 220.84(C) Calculated Loads.
- Section 225.32 Location.
- Revise Section 225.32 in its entirety, as follows:
- Section 230.11 Location of Customer Owned Service Lateral or Drop.
- Add a new Section 230.11, as follows:
- Section 230.70 General.
- Revise Section 230.70, in its entirety.
- Section 230.202 Service-Entrance Conductors.
- Add a new Subsection (C) to Section 230.202.
- Revise Section 230.205(A), as follows:
- Section 230.205(C) Remote Control.
- Revise 230.205(C), as follows:
- (C) Remote Control. For multi-building, industrial installations under single management, the service disconnecting means shall be permitted to be located at a separate building or structure. In such cases, the service disconnecting means shall be per...
- Section 240.6 Standard Ampere Ratings.
- Revise Section 240.6(B) and delete subsection (C), as follows:
- Section 240.86 Series Ratings.
- Revise Section 240.86, as follows:
- Section 250.32(A) Grounding Electrode.
- Revise Section 250.32(A), as follows:
- Section 250.50 Grounding Electrode System.
- Revise Section 250.50, as follows:
- Section 250.52(A)(5) Rod Electrodes.
- Revise Item (5) of Section 250.52(A), in its entirety, as follows:
- Section 250.53 Grounding Electrode System Installation.
- Revise Section 250.53(A), as follows:
- Revise Section 250.53 (B), as follows:
- Revise Sections 250.53(D)(2,) as follows:
- Revise Sections 250.53(E), as follows:
- Revise Section 250.53(G), as follows:
- Section 250.94 Bonding for Other Systems.
- Add new Items (7) & (8) to Section 250.94, as follows:
- Section 250.120(D) Equipment Grounding Conductor
- Add a new Subsection (D) to Section 250.120, as follows:
- Section 310.15(B)(3)(c) Circular Raceways Exposed to Sunlight on Rooftops.
- Revise code section 310.15(B)(3)(c), as follows:
- Section 314.24 Minimum Depth of Boxes for Outlets, Devices, and Utilization Equipment.
- Revise Section 314.24, as follows:
- Section 352.10(F) Exposed.
- Revise Section 352.10(F), as follows:
- (F) Exposed. PVC conduit shall be permitted for exposed work. PVC conduit used exposed in areas of physical damage shall be Schedule 80 and listed as sunlight resistant.
- Informational Note: PVC Conduit, Type Schedule 80, is identified for areas of physical damage.
- Section 358.12 EMT - Uses Not Permitted.
- Add new items (7), (8) and (9) to Section 358.12, as follows:
- (7) Embedded within concrete or masonry in contact with the earth
- (8) Underground installations
- (9) Within earth fills
- Section 514.11(A) General.
- Revise Section 514.11 (A) Circuit Disconnects-General, as follows:
- Revise as follows:
- (B) Visibility. The markings required in 600.4(A) and listing labels shall not be required to be visible after installation but shall be permanently applied in a location visible during servicing. At least one label must be visible at the time of insp...
- Section 600.41(D) Protection.
- Revise Section 600.41(D), as follows:
- Section 680.42(B) Bonding.
- Add Exception No. 2 to Section 680.42(B), as follows:
- 680.42(B) Bonding.
- Bonding by metal-to-metal mounting on a common frame or base shall be permitted.
- Exception No. 1: The metal bands or hoops used to secure wooden staves shall not be required to be bonded as required in 680.26.
- Exception No. 2: A listed self-contained spa or hot tub that meets all of the following conditions shall not be required to have equipotential bonding of perimeter surfaces installed as required in 680.26(B)(2):
- (1) Is installed in accordance with manufacturer’s instructions on or above grade.
- (2) The vertical measurement from all permanent surfaces within 30 horizontal inches (76 cm) of the spa to the top rim of the spa is greater than 28 inches (71 cm).
- Article 682 Natural and Artificially Made Bodies of Water.
- Delete Article 682 in its entirety
- Section 700.1 Scope.
- Revise Section 700.1, as follows:
- Section 700.10(D) Fire Protection.
- Revise Section 700.10(D), as follows:
- Section 700.10(D)(2) Feeder-Circuit Equipment.
- Revise Section 700.10(D)(2) and add a new exception, as follows:
- Section 700.12 General Requirements.
- Revise Section 700.12, as follows:
- Section 700.12(B)(7) Location.
- Add a new Subsection 7 to Section 700.12(B), as follows:
- Add section (A) to Section 800.24
- 800.24 Mechanical Execution of Work. Communications circuits and equipment shall be installed in a neat and workman like manner. Cables installed exposed on the surface of ceilings and sidewalls shall be supported by the building structure in such a ...
- (A) Low voltage cabling installed in a concealed space of a Type I or Type II building shall be non-combustible (plenum rated), or installed in a metal raceway. Cables installed without raceways shall be installed per the manufacturer’s installation i... [Go to Page]